Transmitter W2 & W3 — Wiring & Field Calibration | RCM Flo-Gage™
NCIFLOW.COM | Made in the USA
1+201-419-6111[email protected]
HomeOptionsTransmitter W2 & W3 — Wiring & Calibration

Options — Transmitters

Wiring & CalibrationTransmitter Options W2 & W3

Installation, wiring, and field calibration instructions for the 4–20 mA DC transmitter options fitted inside the Flo-Gage™ enclosure.

1. Installation & Wiring

The transmitter board is fitted inside the enclosure of the Flo-Gage™. Both options use a solid-state strain gage to measure differential pressure directly — independent of the local mechanical indicator.

W2

Option W2

  • 4–20 mA DC output
  • Local mechanical analog readout included
W3

Option W3

  • Operates identically to W2
  • Local mechanical analog output omitted

Transmitter Operation

  • Measures differential pressure directly using a solid-state strain gage
  • Measured DP is independent of the mechanical measurement provided by the local indicator
  • Transmitter output is linear with differential pressure
  • Output must be linearized in the receiving device to provide a flow measurement

Power Requirements

Supply Voltage

24 VDC

External, user-supplied

Min. Current

25 mA

Minimum capacity required

Supplied By

User

Not included with meter

Startup Procedure

  1. 1Pressurize the pipeline.
  2. 2Check the zero.
  3. 3Adjust the zero potentiometer if necessary.

Figure 1 — Connection Diagram

Wiring Connections — Options W2 & W3

24 VDC Power Supply

+Positive terminal → Terminal 2 (+)
Negative terminal → Terminal 1 (–)

Flo-Gage™ Transmitter Terminals

1Terminal 1 — Negative (–)
2Terminal 2 — Positive (+)

Optional Receiving Devices (connected in series)

Digital Readout
DCS Indicators
Additional Receiving Devices

Additional receivers may be connected in series. Observe power supply vs. maximum load impedance limits — see Figure 2.

Adjustment Potentiometers

Span Pot

20 mA adjustment

Zero Pot

4 mA adjustment

Warning: Adjusting the span pot will change meter calibration.

Figure 2 — Loop Impedance vs. Power Supply Voltage

OptionSupply VoltageMaximum Load Impedance
W2 and W324 VDC650 Ω
RW324 VDC350 Ω

When connecting multiple receiving devices in series, ensure the total loop impedance does not exceed the maximum load for your supply voltage.

2. Field Calibration (4–20 mA DC)

2.1 Test Equipment

Recommended: Fluke 9600A digital multimeter or equivalent.

Connect in series with the current loop using the 24 VDC power supply.

2.2 Procedure

All meters are factory calibrated.

Do NOT adjust span unless you are certain the meter is reading incorrectly.

Warning

Do not attempt to adjust the span settings without:

  • Proper test equipment
  • Ability to establish a known steady flow rate close to full scale

Adjustment of the span WILL affect meter calibration.

Zero Calibration

  1. 1Connect multimeter in series with current loop.
  2. 2Pressurize the pipeline.
  3. 3Adjust zero potentiometer until current output reads 4.00 mA ±0.02 mA at no flow.

Span Calibration

  1. 1Establish a known flow rate through the meter — as close to 95% full scale as practical.
  2. 2Set span using the formula below.

Span Calibration Formula

I = 16Q² + 4.00

I = current output in mAQ = decimal % of full scale

Example: at 95% FS → Q = 0.95 → I = 16(0.95)² + 4.00 = 18.44 mA

% Full Scale to Current Output

% Full ScaleCurrent Output (mA)
20%4.64
30%5.44
40%6.56
50%8.00
60%9.76
70%11.84
80%14.24
90%16.96
95%18.44
100%20.00
20%
4.64 mA
30%
5.44 mA
40%
6.56 mA
50%
8.00 mA
60%
9.76 mA
70%
11.84 mA
80%
14.24 mA
90%
16.96 mA
95%
18.44 mA
100%
20.00 mA

Note: Output is non-linear (quadratic) — linearize in receiving device.

W2 & W3 Transmitter FAQ

Common questions about wiring, signal linearization, and calibrating RCM Flo-Gage™ transmitter options W2 and W3.

Wiring & Power

Signal & Linearization

Calibration & Troubleshooting

Have a wiring or calibration question not covered here?

Our engineering team is available Mon–Fri, 8:30am–4:30pm EST.

Need a W2 or W3 Transmitter?

Transmitter options W2 and W3 can be factory-installed on any new Flo-Gage™ order, or retrofitted to existing meters. Contact our engineering team for compatibility and pricing.